-
The 200
amp panel is deficient and undersized service entry due to loads at
existing basement panel, study rooms, or expansions for any reason is
difficult due to this deficiency. If panel is replaced other electric
codes must be met. There is a possibility that a new 200 amp service
could be added for mechanical needs and later upgrade and clean-up the
existing 200 amp service panel.
-
If non metallic domestic water services are
accepted, a grounding field will be required for electric entry.
-
New sub panels at 2ndand 3rdfloors do not have legal panel enclosures and connections: Quantity of
outlet do not meet spacing or user needs. (Room #4) over loaded panels;
over loaded boxes breakers at 2ndfloor are 10
amps and did not shut down when fan melted. Many duplexes are loose or
broken
-
Fire
alarms / Strobes are required for handicap codes and the existing alarm
panel is not expandable.
-
Wire
ground out to conduits / some locations have positive load on white wire
-
Exterior lights - non -WP boxes are missing
connectors and water proof wire; depth of wire below grade is
substandard. Only 5 more hall/ stair lights are needed to complete
lighting upgrade work.
-
Ceiling
fans in study rooms - residential type; illegal mounting and lack
grounding and proper wire switching
-
Basement and 1stfloor old
wire some are not grounded outlet / see sump pit
-
Space
heaters are illegal in fraternities but used.
-
Several
rooms; 4, 12 & 14, have closet lights that are improperly
grounded.
-
The
basement North stair and north exterior wall light wire is shorted to
the conduit and cap off.
-
All
closet lights that are incandescent need to be replaced with code
required fluorescent fixtures and mounted at legal height. Incandescent
lights in hall closets and study rooms are a fire hazard.
-
When the
building meter is removed, the power company noted there is a 127 volt
load on the building when only the main meter is shut off and 52 volts
still remain when the sub-panels are shut off at the basement service
hall. This load should be zero and is particularly dangerous during
fire fighting procedures as well; the white wire maybe
“hot”.
-
New electrical sub panels were added in the early
1990’s at the 1st, 2nd,
and 3rdfloors and panel face to cover splices
should be custom fabricated to comply with NEC.
-
Other problems involve 3rdfloor and some 2ndfloor circuits that do not
properly trip off under fault conditions and a faulty ceiling fan in
room #2 did no cause circuit breaker to shut off in 2004. A light
switch in room 14 caused an immediate fault. The basement disposals in
the Kitchen do not have legal box connections.